Product Highlights

High Efficiency & Energy Saving
Optimized design combined with low-loss silicon steel sheets delivers high operating efficiency and cuts power consumption effectively.

Wide Voltage Compatibility
Available for 3.3kV, 6kV, 6.6kV, 10kV, 11kV and 13.8kV, matching diverse industrial power supply systems.

Flexible Protection Ratings
IP23, IP44, IP54, IP55, IP56 and IPW24 are optional. Ventilation layout and climate protection can be customized on request.

Multiple Cooling Solutions
Support IC01, IC611 and IC81W cooling types, including air-to-air enclosed cooling and air-to-water enclosed cooling structures.

High-Grade Bearing Assembly
Fitted with SKF bearings. Equipped with on-line oil filling and draining device for maintenance without shutdown.

Superior Insulation System
F-class insulation with VPI vacuum pressure impregnation treatment, featuring outstanding moisture resistance, surge withstand and anti-corona performance.

International Standard Compliance
Designed in accordance with GB755, IEC 60034-1 and IEC 60034-5, certified with CCC and CE.

Proven Field Performance
Backed by over 30 years of manufacturing experience. Products have been exported to more than 40 countries and regions globally.

Product Attributes

ItemSpecificationItemSpecification
CustomizationAvailableApplicationGeneral Industrial Use
Operation TypeConstant SpeedModel No.Y630-4-2240KW
PhaseThree-PhaseSeriesY, Y2 Series
Rotor TypeSquirrel-CageEnclosure TypeOpen Type
Pole Number2–12PStarting MethodDOL Direct On-line Starting
CertificatesCCC, CEBrandChangli
Max Rated PowerUp to 250000kWFrequency50Hz / 60Hz
Rated Voltage3.3kV, 6kV, 6.6kV, 10kV, 11kV, 13.8kVFrame Size315–1120mm
Cooling CodeIC01Mounting ArrangementIM1001
RotationCW / CCWDuty CycleS1 Continuous Duty
Insulation ClassFProtection DegreeIP23
Ambient Temperature-20℃ ~ 40℃Installation LocationIndoor & Outdoor
Bearing BrandSKFSpace HeaterIncluded
Export PackingStandard Seaworthy PackingTrademarkCHANGLI
OriginChinaHS Code8501530090
Production Capacity500000 units per year--

Product Description

1. Overview

Our Y series high voltage three-phase squirrel cage induction motor was initially developed and introduced in the 1980s. With more than 30 years of iteration, it benefits from upgraded insulation materials, low-loss silicon steel laminations, enhanced insulation grades and optimized electromagnetic design to reduce losses and boost power density. Drawing on our 60-year accumulated experience in high voltage motor R&D and manufacturing, we have completed the latest design optimization to meet domestic and global industry requirements.

Performance tests verify that this series reaches or approaches the world’s advanced level in both technical and economic indicators. Mass production has been realized, with motors supplied widely across China and exported to over 40 countries and regions covering Europe, America, Africa and other areas, winning consistent positive feedback from end users.

Built with premium raw materials and strict manufacturing processes, the motor features high efficiency, energy saving, low vibration, stable operation and easy installation and maintenance.

Power ratings, electrical characteristics, mounting dimensions and tolerances conform to GB755 Rotating electrical machines – Ratings and performance, IEC 60034-1 Rotating electrical machines – Ratings and performance and relevant machinery industry standards.

Enclosure protection grades follow GB4942.1 and IEC 60034-5. Available options include IP23, IP44, IP54, IP55 and IP56. IP23 motors can be converted to IP44 (pipe ventilation type) or IPW24 (climate protected type). Custom protection classes are available upon request.

Three standard cooling methods are provided per GB/T1993 and IEC 60034-6: IC01, IC611 and IC81W. Alternative cooling configurations can be offered as required.

The basic construction and mounting form is IMB3 horizontal foot-mounted, complying with GB997 and IEC 60034-7 for motor construction and mounting type codes.

Based on rotor type, protection grade and cooling method, the family is divided into 8 sub-series as shown below:

ModelProtection ClassCooling MethodSquirrel Cage RotorWound Rotor
Damp ProofIP23IC01Y SeriesYR Series
Climate ProtectedIPW24IC01YQF SeriesYRQF Series
Air-Water Cooled EnclosedIP44, IP54, IP55, IP56IC81WYKS SeriesYRKS Series
Air-Air Cooled EnclosedIP44, IP54, IP55, IP56IC611YKK SeriesYRKK Series

The technical data and installation dimensions of the 10kV motors listed can be adapted for 3kV, 10.5kV and 11kV variants across all frame sizes.

2. Application

This HV motor is widely used to drive compressors, fans, water pumps, feeders, conveyors and other general machinery. It serves as the prime mover for mines, machinery plants, petrochemical facilities, power stations and other industrial and mining sites.

For loads with high inertia such as blowers, coal mills, rolling mills, crushers and belt conveyors, customers shall submit complete technical data and sign a technical agreement with us. This supports customized design and guarantees stable motor operation.

Standard Operating Conditions

  1. Altitude ≤ 1000 m
  2. Maximum ambient temperature ≤ 40℃; minimum ambient temperature: -15℃ for rolling bearing motors, 5℃ for sliding bearing motors; YKS / YRKS minimum ambient temperature: 5℃
  3. For YKS and YRKS water-cooled motors: cooling water inlet temperature 5℃ ~ 33℃
  4. Average monthly maximum relative humidity ≤ 90%, with average monthly minimum temperature ≤ 25℃
  5. Supply frequency: 50Hz ±1%
  6. Operating voltage deviation: within ±5% of rated voltage
  7. Duty: S1 continuous operation

3. Construction Features

Y and YR are the base series with IP23 protection and IC01 cooling. Derivative models include YKS air-water cooled, YQF climate protected, YKK air-air cooled, as well as YRKS, YRQF and YRKK wound rotor versions.

It adopts internationally popular box-type construction. Frame and end shields are steel plate welded for high rigidity and low weight. After removing the guard or cooler, internal inspection and access are straightforward, simplifying installation and maintenance.

The stator adopts external pressing structure. Stator windings use F-class insulation and anti-corona materials. Terminal connections are secured with special binding technology. The whole stator undergoes VPI vacuum pressure impregnation with solventless F-class varnish, delivering reliable insulation, moisture resistance and surge withstand capability.

Squirrel cage rotors are mostly cast aluminum type with a proven zero breakage record for reliable running. Copper bar squirrel cage rotors use advanced, robust welding and slot fixing technology. Wound rotors also adopt F-class insulation and VPI treatment.

Two bearing types are optional: rolling bearing and sliding bearing, selected according to motor power and speed. Base bearing protection is IP44; higher motor protection grades come with upgraded bearing sealing accordingly.

Rolling bearing units are fitted with on-line oil filling and draining ports. Special tools allow grease replenishment and discharge without machine shutdown.

The main terminal box is sealed at IP54. It is normally mounted on the right side (viewed from the drive end), and can be rearranged to the left side on request. Cable entry direction can be adjusted to top, bottom, left or right. Independent earthing terminals are built inside the box.

4. Starting Guidance for Y, YKS, YQF, YKK Induction Motors

Finite element thermal and stress simulation is applied to squirrel cage rotors to avoid premature damage caused by starting overload. Please comply with the following requirements:

  1. The total inertia of driven equipment (referred to motor speed) shall not exceed the allowable load inertia J listed in technical datasheets.
  2. Terminal voltage during starting shall remain no lower than 85% of rated voltage.

The above starting specification applies to typical quadratic torque loads such as pumps and fans.
Under these conditions, the motor permits two consecutive cold starts or one hot start, with natural coast-down between attempts. Additional restarting is only allowed after a 1-hour cooling period.

If the load inertia exceeds the specified value, frequent starting is required, or heavy-load starting is needed, contact our engineering team for customized design confirmation.

Product Parameters

Frame Size: H355–1120
Rated Voltage: 3kV, 3.3kV, 5.5kV, 6kV, 6.6kV, 10kV, 11kV, 13.8kV
Poles: 2P,4P,6P,8P,10P,12P,14P,16P
Protection Degree: IP23, IPW24
Mounting Types: IMB3, IMB35, IMB5, IMV1 etc.
Power Range: up to 25000kW
Frequency: 50Hz, 60Hz
Cooling Method: IC01

Packaging & Shipping

Export standard seaworthy packing
Plywood case or fumigated wooden case
Suitable for long-distance sea transportation

Quality Control

All measuring and test instruments are calibrated annually. Every component and process is subject to strict inspection.


PartInspection Items
Coil1. Raw material physical & chemical test2. Winding process audit3. Winding dimension check
Iron Core1. Silicon steel material test report2. Lamination burr & coating inspection3. Stack dimension verification
Frame1. Welded structure conformity certificate2. Finishing dimensional inspection
Rotor1. Core stacking inspection2. Conductor bar welding check3. Bar & end ring material, appearance, conductivity and dimension test4. Slot bar fastening check5. Outer diameter and overall dimension check6. Dynamic balancing correction
Shaft1. Raw material and annealing inspection2. Finishing dimension check
Stator1. Core compaction check2. Core length and segment length inspection3. Winding insertion inspection4. Core loss test
Assembly1. Plain bearing dimension and surface quality check2. Air gap, stator-rotor alignment, fan and shroud clearance check3. Internal cleanliness inspection4. Shaft centre height and mounting dimension check
Final Test1. Routine test2. Type test

Routine Test Items

  • Three-phase DC resistance of windings
  • Winding insulation resistance to earth
  • Winding withstand voltage test
  • No-load current
  • No-load power
  • No-load loss
  • Three-phase no-load current unbalance
  • Locked rotor current
  • Locked rotor torque
  • Breakdown torque
  • Rotation direction
  • Vibration measurement (horizontal, vertical, axial)
  • Noise test

Type Test Items

  • Full-load input power
  • Full-load current
  • Stator winding loss
  • Rotor winding loss
  • Iron loss
  • Mechanical loss
  • Stray load loss
  • Full-load slip
  • Stator winding temperature rise
  • Bearing temperature rise
  • Hot insulation resistance
  • Overload test
  • Full-load power factor
  • Efficiency

Every motor undergoes full routine testing before shipment. A formal test report will be supplied with each unit upon passing inspection.

Warranty

Standard warranty: 12 months after commissioning or 18 months after delivery, whichever occurs first.
Extended warranty terms are available, please contact us for details.


0
Inquire for more cooperation or product information.
We will contact you within 1 working day, please check your email.
2240kW Three Phase HV AC Squirrel Cage Induction Motor
Company Name
Name
Mail
Mobile phone
Message
Send

Weigao

We reply immediately
Welcome to our website. Ask us anything 🎉

Start Chat with: